p&id symbols, Piping and Instrumentation Diagrams or simply P&IDs are the “schematics” used in the field of instrumentation and control (Automation).
The P&ID is used to by field techs, engineers, and operators to better understand the process and how the instrumentation is inter connected.
Most industries have standardized the symbols according to the ISA Standard S5.1 Instrumentation Symbol Specification.
- Piping & Instrumentation Drawing (original)
- Process & Instrumentation Diagram (also used)
- Process Flow Diagram – PFD (simplified version of the P&ID)
Temperature Process
Using pictorial diagrams may be informative however it is not practical or CAD friendly especially in a multi-loop process.
Building the P&ID
The P&ID will use symbols and circles to represent each instrument and how they are inter-connected in the process.
Tag Numbers
Tag “numbers” are letters and numbers placed within or near the instrument to identify the type and function of the device.
Tag Descriptors
1 . The first letter is used to designate the measured variable
Pressure
Level
Flow
Temperature
Indicator
Recorder
Controller
Transmitter
2. The succeeding letter(s) are used to designate the function of the component, or to modify the meaning of the first letter.
Indicator
Recorder
Controller
Transmitter
Tag Numbers
Tag “numbers” are letters and numbers placed within or near the instrument to identify the type and function of the device.
ISA S5.1 Identification Letters
First – Letter | Succeeding – Letters | ||||
Measured or Initiating Variable | Modifier | Readout Function | Output Function | Modifier | |
A | Analysis | ||||
C | Control | ||||
D | Differential | ||||
F | Flow Rate | Ratio | |||
H | Hand | High | |||
I | Current | Indicate | |||
L | Level | Low | |||
P | Pressure, Vacuum | ||||
Q | Quantity | Totalizer | |||
S | Safety | Switch | |||
T | Temperature | Transmit | |||
V | Vibration | Valve, Damper | |||
Z | Position | Actuator | |||
Examples
Instrument Location
The presence or absence of a line determines the location of the physical device. For example no line means the instrument is installed in the field near the process.
Shared Displays/Shared Control
Some instruments are part of a Distributed Control System (DCS) where a specific controller or indicator can be selected from many others but shown in one location (like a terminal screen)
Summary of instrument type & location
Piping and Connection Symbols
These symbols are used to identify how the instruments in the process connect to each other.
And what type of signal is being used. (electrical, pneumatic, data, etc.
Valve Symbols
P&ID Example
P&ID Exercise
Process Flow Diagram – PFD
A PFD shows less detail than a P&ID and is used only to understand how the process works